Cooling tower Process Flowsheets & Simulations
Explore 2 validated, solved Cooling tower simulation flowsheets in MaximaLabs — real components: ethanol, water. Open any one directly in your browser.
Solved via: NRTL, STEAM.
Cooling-water tower (Merkel sizing)
A process cooling-water utility: a hot ethanol-water process stream is cooled against cooling water in a counter-current exchanger, and the warmed cooling water is then sent to an evaporative cooling tower that rejects the picked-up heat to ambient air and returns it cold. The tower reports the evaporation + blowdown makeup water and — because the wet-bulb temperature and the water-to-air ratio L/G are given — the Merkel tower characteristic KaV/L a designer sizes the fill to, plus the range (hot→cold water drop, 10 K here) and the approach to the wet-bulb (5 K). Rate a fill against that demand with the standalone Cooling tower (Merkel) analysis tool. Honest scope: the cooling-water side is shown open (supply → exchanger → tower → return); a real plant recycles the return with makeup, and the Merkel model carries Le=1 assumptions.
6 unit ops • NRTL
79 1
View & openHybrid cooling — a closed circuit isolated from the tower by a plate exchanger
Three loops in series, and the middle one is the point. The process is cooled by a closed circuit of treated water that never contacts air; that circuit rejects its heat across a plate exchanger into an open evaporative circuit; and only that outer circuit goes to the tower and loses water. Why a plant pays for the extra exchanger: open cooling water picks up oxygen, airborne dirt and biology, and concentrates its dissolved salts every cycle. Putting that water through a reactor jacket or a condenser is what fouls and corrodes them. The closed loop stays clean, stays at pressure, and its inventory never concentrates — so the equipment the process actually touches sees water that does not scale. Solved here: the process leaves at 318 K, the closed circuit picks that up (303 → 320 K) and is knocked back to 306 K across the plate exchanger, the open circuit takes it (301 → 311 K) and the tower returns it to 301.15 K at a 4.0 K approach to a 297.15 K wet bulb. Water loss appears only in the open circuit — the closed one leaves with exactly the flow it entered with, which is the whole claim made arithmetic. The tower also reports its scaling limit from the makeup analysis: this water saturates in calcite at 2.2 cycles, so the 4 cycles configured here shows negative headroom — a real operating conflict, left visible rather than tuned away. Bounded: steady state, so there is no basin inventory and no level control (a level is only meaningful in the dynamic engine). Fouling is not modelled — the argument for the closed loop is made by the chemistry, not by a fouling rate. Feeds and returns are open rather than recycled, the same convention cooling-water-tower uses.
10 unit ops • STEAM
22 1
View & open