MaximaLabs
All unit operations

Air cooler (fin-fan) simulation

1 inlet -> 1 outlet (rejects to air)

Governing equations

The exact equations the solver works for a air cooler (fin-fan) — the same math shown in the app's "Theory" panel, not a black box.

Q=F(hinhout)(heat rejected to air)Q = F\,(h_{in} - h_{out}) \quad (\text{heat rejected to air})
Q=m˙aircp,air(Tair,outTair,in)Q = \dot m_{air}\,c_{p,air}\,(T_{air,out} - T_{air,in})
QQ
heat rejected to the air [W]
FF
process molar flow [mol/s]
hh
process molar enthalpy [J/mol]
m˙air\dot m_{air}
air mass flow [kg/s] — solved from the air-side balance
cp,airc_{p,air}
air heat capacity [J/kg/K] (≈1005)
Tair,inT_{air,in}
ambient air inlet temperature [K]
Tair,outT_{air,out}
air outlet temperature [K]

Parameters

process side: exactly one of duty [W, negative] OR outlet_temperature [K] + optional pressure_drop [Pa]. Air side: air_inlet_temperature [K, ambient, default 308.15]; one of air_mass_flow [kg/s] / air_outlet_temperature [K] / air_temperature_rise [K, default 15]. Optional fan_static_pressure_pa [Pa] + fan_efficiency [default 0.65] for fan power. Rejects the process heat to ambient air (fin-fan); cannot cool below ambient